Related Electrical Questions
I want to run direct burial wire to workshop/man cave. What
I want to run direct burial wire to workshop/man cave. What size wire and sub panel for a 150' run. Also what size breaker for main panel? … read more
Kevin
Kevin
Licensed Electrical Contractor
Diploma
7,655 satisfied customers
Can I run a 60amp sub panel from my main panel to my garage
Can I run a 60amp sub panel from my main panel to my garage to power my small workshop and a 50amp breaker for a hot tub? Other than the 50amp breaker, I would have a couple 20amp breakers and a coupl… read more
Wire Guy Franklin
Wire Guy Franklin
Business Owner
Master Electrician
1,972 satisfied customers
I have a 10 year old GE Powermark Goldcenter panel
I have a 10 year old GE Powermark Goldcenter panel TLM1212CCU Mod 1 and would like to install AFCI's. I can't find a spec sheet for the panel. Where can I get one. … read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I am needing to install 2-220 volt outlast for my table saw
I am needing to install 2-220 volt outlast for my table saw and dust collector in my woodworking shop. Currently have 8 gauge coming from house to garage with small 4 fuse box. I will be having fuse b… read more
Kevin
Kevin
Licensed Electrical Contractor
Diploma
7,655 satisfied customers
I would like to run electrical service to the basement I'm
I would like to run electrical service to the basement I'm finishing.1. Is there a recommended service level (eg, 125A)? 2. Based on the recommended service, what's the best cable? The run will be ind… read more
Kevin
Kevin
Licensed Electrical Contractor
Diploma
7,655 satisfied customers
I live in Nashville, TN. I have a 1985 200 amp main panel in
I live in Nashville, TN. I have a 1985 200 amp main panel in my home. I need to run a sub panel approx. 70 feet away. From the sub panel I plan on 4 to 5 outlets on two or 3 20 breakers using 12-2 rom… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I actually have 2 questions a detached working shop. I plan
I actually have 2 questions for wiring a detached wood working shop. I plan to have 10 outlets. 1 for a small fridge and window a/c, 1 for a 2nd dust collector and 1 for a air filter. Rest for various… read more
Kevin
Kevin
Licensed Electrical Contractor
Diploma
7,655 satisfied customers
Good morning and Merry Christmas/Happy Holidays. I have a
Good morning and Merry Christmas/Happy Holidays. I have a few questions regarding the sizing of an electrical sub-panel. I am building a small workshop in my basement and wish to provide lighting, a d… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I have a stand-alone workshop that is wired with two 20 amp
I have a stand-alone workshop that is wired with two 20 amp circuits (12 gauge grounded). To hook up the subpanel in the workshop I need to run service cable from my main panel in our house to the sub… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
HI I have a 100 amp service in our house and want to put a
HI I have a 100 amp service in our house and want to put a sub panel in the garage for my workshop. I have a 220V table saw, 2 hp dust collection system, plus 7.5 amp compressor, plus lights and other… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I have to add a sub panel to the basement, the main panel is
I have to add a sub panel to the basement, the main panel is full, i have a 200 amp service to the house. There is a sub panel in the garage. I don't want to connect anything just have to string in th… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I have a 200 amp main breaker box in my house with a 125 amp
I have a 200 amp main breaker box in my house with a 125 amp sub panel in my garage. The subpanel is protected by a 50 amp breaker (wired for 120 or 240) in the main panel. I am wanting to add a heate… read more
Tommy Tesla
Tommy Tesla
Electrical Contractor
Vocational, Technical or Trade Scho
139 satisfied customers
Hi. I have added a 220v dust collector to a home workshop.
Hi. I have added a 220v dust collector to a home workshop. I have a 220v 12a table saw currently, on a dedicated circuit. There is a 20 amp double pole breaker at the panel (200a service), with 10 ga … read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I need to run a line from the main breaker box at my house
I need to run a line from the main breaker box at my house to a new work shop. I want to have 220V at the shop to run a 5hp table saw, 5hp planer and a 4hp air compressor plus 110V for small tools and… read more
Joseph
Joseph
743 satisfied customers
I have an existing 150 amp main service in my house. I would
I have an existing 150 amp main service in my house. I would like to run a 100 amp subpanel to my garage. Would it be acceptable to do this given the main service is only rated for 150 amps? Should I … read more
Joseph
Joseph
743 satisfied customers
what size wire and what size breaker should I use to run service
what size wire and what size breaker should I use to run service from my 200 Amp main box to a subpanel in the basement, 20 foot run, for about 5 lighting circuits Read more: http://www.answers.com/wh… read more
Jason
Jason
Service Technician
Associate Degree
4,922 satisfied customers
Hi, I want to feed a 100 amp subpanel in my garage from a 200
Hi, I want to feed a 100 amp subpanel in my garage from a 200 amp main panel in my basement. The total cable length will be 50 feet and the garage is attached to the house via a mud room. My questions… read more
Sir Sparks
Sir Sparks
Owner
State & UK Certified Master electri
2,519 satisfied customers
I bought a welder for my garage and I need to know what size
I bought a welder for my garage and I need to know what size and type breakers I need I have a breaker box in the garage that is fed from the house. There is a 40 amp breaker in the main breaker box i… read more
Jason
Jason
Service Technician
Associate Degree
4,922 satisfied customers
Disclaimer: Information in questions, answers, and other posts on this site ("Posts") comes from individual users, not JustAnswer; JustAnswer is not responsible for Posts. Posts are for general information, are not intended to substitute for informed professional advice (medical, legal, veterinary, financial, etc.), or to establish a professional-client relationship. The site and services are provided "as is" with no warranty or representations by JustAnswer regarding the qualifications of Experts. To see what credentials have been verified by a third-party service, please click on the "Verified" symbol in some Experts' profiles. JustAnswer is not intended or designed for EMERGENCY questions which should be directed immediately by telephone or in-person to qualified professionals.

JustAnswer in the News:

Ask-a-doc Web sites: If you've got a quick question, you can try to get an answer from sites that say they have various specialists on hand to give quick answers... Justanswer.com.
JustAnswer.com...has seen a spike since October in legal questions from readers about layoffs, unemployment and severance.
Web sites like justanswer.com/legal
...leave nothing to chance.
Traffic on JustAnswer rose 14 percent...and had nearly 400,000 page views in 30 days...inquiries related to stress, high blood pressure, drinking and heart pain jumped 33 percent.
Tory Johnson, GMA Workplace Contributor, discusses work-from-home jobs, such as JustAnswer in which verified Experts answer people’s questions.
I will tell you that...the things you have to go through to be an Expert are quite rigorous.

What Customers are Saying:

You did one super job of explaining to me everything there is to know about this fridge. I'm looking forward to asking you questions in the future.

JimmyBagley, IA

Wonderful service, prompt, efficient, and accurate. Couldn't have asked for more. I cannot thank you enough for your help.

Mary C.Freshfield, Liverpool, UK

This expert is wonderful. They truly know what they are talking about, and they actually care about you. They really helped put my nerves at ease. Thank you so much!!!!

AlexLos Angeles, CA

Thank you for all your help. It is nice to know that this service is here for people like myself, who need answers fast and are not sure who to consult.

GPHesperia, CA

I couldn't be more satisfied! This is the site I will always come to when I need a second opinion.

JustinKernersville, NC

Just let me say that this encounter has been entirely professional and most helpful. I liked that I could ask additional questions and get answered in a very short turn around.

EstherWoodstock, NY

Thank you so much for taking your time and knowledge to support my concerns. Not only did you answer my questions, you even took it a step further with replying with more pertinent information I needed to know.

RobinElkton, Maryland

< Previous | Next >

Meet the Experts:

Mike

Mike

Master Electrician

1,426 satisfied customers

Licensed Master Electrician - OnQ Certified Data Voice Audio Video Installer

Jason

Jason

Service Technician

4,922 satisfied customers

Over 20 years of experience in all types of installations, troubleshooting, and repairs.

Mike G.

Mike G.

Master Electrician

9,751 satisfied customers

Proven Professional 49 years Experience

Kevin

Kevin

Licensed Electrical Contractor

7,655 satisfied customers

34 years Licensed Electrical Contractor in Illinois, Adjunct College Electrical Instructor, Former Electrical Inspector, Diploma: Digital Electronics, FCC Amateur & Commercial Radio Licenses

electrifier

electrifier

Master Electrician

1,458 satisfied customers

Electrical contractor and electrical inspector for over 24 years with phone and networking expertise

Rich

Rich

Master Electrician

1,117 satisfied customers

Over 35 years residential, commercial, industrial wiring, install, troubleshoot, service, maintain

mrromex

mrromex

Electrical Technician

281 satisfied customers

over 40 years of all phases related to residential wiring and remodeling

< Previous | Next >

Disclaimer: Information in questions, answers, and other posts on this site ("Posts") comes from individual users, not JustAnswer; JustAnswer is not responsible for Posts. Posts are for general information, are not intended to substitute for informed professional advice (medical, legal, veterinary, financial, etc.), or to establish a professional-client relationship. The site and services are provided "as is" with no warranty or representations by JustAnswer regarding the qualifications of Experts. To see what credentials have been verified by a third-party service, please click on the "Verified" symbol in some Experts' profiles. JustAnswer is not intended or designed for EMERGENCY questions which should be directed immediately by telephone or in-person to qualified professionals.