Need an electrician. Today. Ballast change from magnetic to
Yes Ballast change from magnetic to electronic Magnetic wiring was 1 blue 1 red 1 black 1 white New electronic ballast is 2 blue 1 red 1 blackb1 white. Fixture is connected in series and is f96t12 8ft 60 watt 2 bulbs. Fixture has 1 red 1 blue on one end and 1 black and 1 white on the other end. How do the wires connect. The new ballast is a pro12 2N rated for f96t12 8ft Bulbs are f96t12 cw/ew… read more
David Bowden
David Bowden
Owner
6,162 satisfied customers
I have a wired in series 8 ft fluorescent F96t12 -2 lamp
I have a wired in series 8 ft fluorescent F96t12 -2 lamp fixtures that I need to replace the ballast from magnetic to electronic. This is in an old building where the fixtures only have 1-red/1-blue w… read more
Jason
Jason
Service Technician
Associate Degree
4,922 satisfied customers
I need the wiring diagram for an electronic ballast which
I need the wiring diagram for an electronic ballast which has fewer wires than the old magnetic ballast … read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I need help wiring a quicktronic tap 2x96t12 unv, I am a pro
I need help wiring a quicktronic tap 2x96t12 unv JA: How old is the system in question? And have you consulted an electrician yet? Customer: I am a pro handyman...no and I won't JA: Do you plan on doi… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I am changing out a keystone 120TP magnetic ballast to a
I am changing out a keystone 120TP magnetic ballast to a keystone KTEB-120-1-TP-EMI electronic ballast and am having trouble with the wiring. Can you help?… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I am replacing an old ballast for a T12 single tube
I am replacing an old ballast for a T12 single tube florescent (Keystone Transformers RSL40) now out of production. Found what is listed as replacement electronic ballast on Ballastshop.com - KTEB-140… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
Trying to wire in a new ballast on a F96T12 light fixture.
trying to wire in a new ballast on a F96T12 light fixture. Ballast has 2 blues and 1 red on one end and 1 white, 1 black on the other end. Fixture on one the sockets have 1 red, 1 blue. Opposing end h… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
F96T12 MAGNETIC BALLASTS TO ELECTRONIC. THE ELECTRONIC ONE
IM CHANGING F96T12 MAGNETIC BALLASTS TO ELECTRONIC. THE ELECTRONIC ONE HAVE ON RED AND TWO BLUE ON ONE SIDE AND ON BLACL AND ONE WHITE ON THE OTHER. WHAT THE WIRING DIAGRAM PLEASE? … read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I have a barn with several lights that each have 2
I have a barn with several lights that each have 2 florescent F96T12 bulbs. One light is not working. Neither bulb lights; one bulb just barely flickers. I've replaced the bulbs and it still doesn't w… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I'm replacing a ballast on a single tube 4 ft flourescent
i'm replacing a ballast on a single tube 4 ft flourescent fixture. the fixture has 2 blue wires but the ballast only has 1 blue wire … read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
Magnetic to electronic ballast wiring JA: Sometimes electrical
old ballast has 1 white and 1 black wire on one end then one red and one blue on the other end. my lights are the single pin florescent type. my new electronic ballast has 1 white, 1 black, 2 yellow, 2 red, and 2 blue wires … read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
The ECN-2P60-SC has 2 blue wires instead of one like my old
The ECN-2P60-SC has 2 blue wires instead of one like my old ballast but my fixture has 2 bulbs in it. Where does the other blue wire go… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I'm replacing a Mark III Energy Saver ballast R-2E75-S-TP on
I'm replacing a Mark III Energy Saver ballast R-2E75-S-TP on a 2 lamp fixture that has 2 f96T12 lamps. THe old ballast has 1 ea. Bl. WH. RRed, Blue wires. The new one has BL. Wh. 2 yellow , 2 Red and … read more
AssuredElectrical
AssuredElectrical
Electrical Contractor
High School or GED
3,844 satisfied customers
I am changing out a magnetic ballast with an electronic ballast
I am changing out a magnetic ballast with an electronic ballast for a 2 lamp (f96t12) fixture. The ballast has 2 blue wires, 1 red, 1 black and 1 white wire. My fixture has 4 sockets, one socket has a… read more
AssuredElectrical
AssuredElectrical
Electrical Contractor
High School or GED
3,844 satisfied customers
I am switching out a magnetic F96T12 to electronic. White to
I am switching out a magnetic F96T12 to electronic. White to white. Black to black. I have One lamp socket with red and one socket with blue. Ballast has one red and 2 blues. What do I do?… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
I also an converting a magnetic ballast to an elctronic ballast on
I also an converting a magnetic ballast to an elctronic ballast on old one end has black, white, blue other 2 reds new ballast one end black & white other two blue & 1 red wire… read more
AssuredElectrical
AssuredElectrical
Electrical Contractor
High School or GED
3,844 satisfied customers
I am changing out a Magnetic ballast, F96T12 8 2 lamp fixture.
I am changing out a Magnetic ballast, F96T12 8' 2 lamp fixture. What is the new wiring diagram? My ballast has a white, black, red on one end and 2 blues on other end. Tell me color wires to connect t… read more
Alex
Alex
Owner
Bachelor's Degree
1,783 satisfied customers
I replaced magnetic ballasts with electronic ballasts in a
I replaced magnetic ballasts with electronic ballasts in a pair of parallel-wired two bulb F96T12 fixtures in my brother's shop. I wired them using the pattern of the magnetic ballasts I took out, (2 … read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,751 satisfied customers
Disclaimer: Information in questions, answers, and other posts on this site ("Posts") comes from individual users, not JustAnswer; JustAnswer is not responsible for Posts. Posts are for general information, are not intended to substitute for informed professional advice (medical, legal, veterinary, financial, etc.), or to establish a professional-client relationship. The site and services are provided "as is" with no warranty or representations by JustAnswer regarding the qualifications of Experts. To see what credentials have been verified by a third-party service, please click on the "Verified" symbol in some Experts' profiles. JustAnswer is not intended or designed for EMERGENCY questions which should be directed immediately by telephone or in-person to qualified professionals.

JustAnswer in the News:

Ask-a-doc Web sites: If you've got a quick question, you can try to get an answer from sites that say they have various specialists on hand to give quick answers... Justanswer.com.
JustAnswer.com...has seen a spike since October in legal questions from readers about layoffs, unemployment and severance.
Web sites like justanswer.com/legal
...leave nothing to chance.
Traffic on JustAnswer rose 14 percent...and had nearly 400,000 page views in 30 days...inquiries related to stress, high blood pressure, drinking and heart pain jumped 33 percent.
Tory Johnson, GMA Workplace Contributor, discusses work-from-home jobs, such as JustAnswer in which verified Experts answer people’s questions.
I will tell you that...the things you have to go through to be an Expert are quite rigorous.

What Customers are Saying:

You did one super job of explaining to me everything there is to know about this fridge. I'm looking forward to asking you questions in the future.

JimmyBagley, IA

Wonderful service, prompt, efficient, and accurate. Couldn't have asked for more. I cannot thank you enough for your help.

Mary C.Freshfield, Liverpool, UK

This expert is wonderful. They truly know what they are talking about, and they actually care about you. They really helped put my nerves at ease. Thank you so much!!!!

AlexLos Angeles, CA

Thank you for all your help. It is nice to know that this service is here for people like myself, who need answers fast and are not sure who to consult.

GPHesperia, CA

I couldn't be more satisfied! This is the site I will always come to when I need a second opinion.

JustinKernersville, NC

Just let me say that this encounter has been entirely professional and most helpful. I liked that I could ask additional questions and get answered in a very short turn around.

EstherWoodstock, NY

Thank you so much for taking your time and knowledge to support my concerns. Not only did you answer my questions, you even took it a step further with replying with more pertinent information I needed to know.

RobinElkton, Maryland

< Previous | Next >

Meet the Experts:

Mike

Mike

Master Electrician

1,426 satisfied customers

Licensed Master Electrician - OnQ Certified Data Voice Audio Video Installer

Jason

Jason

Service Technician

4,922 satisfied customers

Over 20 years of experience in all types of installations, troubleshooting, and repairs.

Mike G.

Mike G.

Master Electrician

9,751 satisfied customers

Proven Professional 49 years Experience

Kevin

Kevin

Licensed Electrical Contractor

7,497 satisfied customers

34 years Licensed Electrical Contractor in Illinois, Adjunct College Electrical Instructor, Former Electrical Inspector, Diploma: Digital Electronics, FCC Amateur & Commercial Radio Licenses

electrifier

electrifier

Master Electrician

1,458 satisfied customers

Electrical contractor and electrical inspector for over 24 years with phone and networking expertise

Rich

Rich

Master Electrician

1,117 satisfied customers

Over 35 years residential, commercial, industrial wiring, install, troubleshoot, service, maintain

mrromex

mrromex

Electrical Technician

281 satisfied customers

over 40 years of all phases related to residential wiring and remodeling

< Previous | Next >

Disclaimer: Information in questions, answers, and other posts on this site ("Posts") comes from individual users, not JustAnswer; JustAnswer is not responsible for Posts. Posts are for general information, are not intended to substitute for informed professional advice (medical, legal, veterinary, financial, etc.), or to establish a professional-client relationship. The site and services are provided "as is" with no warranty or representations by JustAnswer regarding the qualifications of Experts. To see what credentials have been verified by a third-party service, please click on the "Verified" symbol in some Experts' profiles. JustAnswer is not intended or designed for EMERGENCY questions which should be directed immediately by telephone or in-person to qualified professionals.