I'm going to be moving into an apartment and the only 240v

Customer Question

Hi mike, I'm going to be moving into an apartment and the only 240v power supply is a 40a breaker for a range oven. I have an electric brewery controller with 30a wiring, can I run this equipment off the 40a breaker without causing a hazard?
Submitted: 2 years ago.
Category: Electrical
Expert:  Mike G. replied 2 years ago.

Hi, I'm Mike G and I be glad to assist you. If the equipment is listed 30A, the circuit needed is a 40A. That is 30X 1.25 continuous= 37.5A and you step up to the breaker 40A.

Customer: replied 2 years ago.
Ok, so even though the wiring is rated for 30a, I'll be good with a 40a breaker. Also, I want to provide myself with GFI protection. Can I build an inline GFI power cord with a 40a plug wired into a 50a GFI spa panel, and have a 10/4 30a extension cord running from the panel and plugged into my controller?
Expert:  Mike G. replied 2 years ago.

Yes you can.