I replaced ballast and bulbs in a two light T12 florescent
I replaced ballast and bulbs in a two light T12 florescent fixture. When I through the switch, the lights turn on (not full length of bulb, just about 1/3) and then immediately turn off. … read more
Sam I
Sam I
Electrician
Bachelor's Degree
2,265 satisfied customers
I need advice on how to wire a new ballast for a twin 8 ft
I need advice on how to wire a new ballast for a twin 8 ft fluorescent, the old one has a black and white wires at one end, same as with the new one, but the new one has TWO blue wires and a red at th… read more
Kevin
Kevin
Licensed Electrical Contractor
Diploma
6,877 satisfied customers
I am replacing an old ballast for a T12 single tube
I am replacing an old ballast for a T12 single tube florescent (Keystone Transformers RSL40) now out of production. Found what is listed as replacement electronic ballast on Ballastshop.com - KTEB-140… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,821 satisfied customers
Magnetic to electronic ballast wiring JA: Sometimes electrical
old ballast has 1 white and 1 black wire on one end then one red and one blue on the other end. my lights are the single pin florescent type. my new electronic ballast has 1 white, 1 black, 2 yellow, 2 red, and 2 blue wires … read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,821 satisfied customers
I have a GE249RES120- Ballast I bought. It is "supposed" to
I have a GE249RES120-B Ballast I bought. It is "supposed" to be for 1 or 2 bulbs. I have only 1 bulb, but the ballast has extra wires for the other light. How does this work?… read more
mstr_elec
mstr_elec
25 satisfied customers
I have a ge ballast model ge260ismv-n-diyb . 2 lamp fixture
I have a ge ballast model ge260ismv-n-diyb . 2 lamp fixture with 2f96t12 bulbs. One bulb lights. When I remove the lit bulb the other bulb lights. But both will not light at the same time.. They are 7… read more
AssuredElectrical
AssuredElectrical
Electrical Contractor
High School or GED
3,844 satisfied customers
I am changing out a magnetic ballast with an electronic ballast
I am changing out a magnetic ballast with an electronic ballast for a 2 lamp (f96t12) fixture. The ballast has 2 blue wires, 1 red, 1 black and 1 white wire. My fixture has 4 sockets, one socket has a… read more
AssuredElectrical
AssuredElectrical
Electrical Contractor
High School or GED
3,844 satisfied customers
On 1 end of fixture the bulb holders have a black and a white
On 1 end of fixture the bulb holders have a black and a white wire. Do I connect the black and white together on each holder and then connect the red from the ballast to the 4 wires?… read more
AssuredElectrical
AssuredElectrical
Electrical Contractor
High School or GED
3,844 satisfied customers
I am changing an old GE magnetic ballast in a T12, 8FT. 2 lamp
I am changing an old GE magnetic ballast in a T12, 8FT. 2 lamp fixture to an electronic ballast. The old ballast has the black and white wires on one side and a blue and a red wire on the other side. … read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,821 satisfied customers
have lighting. ballast needs to be repaced. 2 - 26 watt cfl
have lighting. ballast needs to be repaced. 2 - 26 watt cfl lights 277 volts How do I remove so emergency ballast does not arc… read more
AssuredElectrical
AssuredElectrical
Electrical Contractor
High School or GED
3,844 satisfied customers
This GE 140RS120 wont light. Both sockets changed out with
This GE 140RS120 won't light. Both sockets changed out with two blue wires inserted into one end of a new T12 socket and two red inserted into the other new socket. The line wires connected obviously.… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,821 satisfied customers
I have an old desk lamp, two 18" bulbs, and a push-button on/off
I have an old desk lamp, two 18" bulbs, and a push-button on/off switch (one red button, one black). It has two ballasts in it. It's not working, and I suspect it's the ballasts? What do you think?… read more
Jason
Jason
Service Technician
Associate Degree
4,922 satisfied customers
I have a GE 296HO-MV-N-DIY ballast. Will it replace a B260112OMA
I have a GE 296HO-MV-N-DIY ballast. Will it replace a B260112OMA Basic 12 ballast made by Universal Lighting Technologies. The GE has two red, two blue, and two yellow wires along with the black and w… read more
Jason
Jason
Service Technician
Associate Degree
4,922 satisfied customers
I just got a new OSRAM EZ-PLUS electronic ballast and cannot
I just got a new OSRAM EZ-PLUS electronic ballast and cannot understand their wiring diagram for the output (lamp side) as there is only 3 outlets whereas a fluorescent lamp has 4 pins?… read more
Alex
Alex
Owner
Bachelor's Degree
1,783 satisfied customers
I bought a GE T8 G8 432 ballast to replace three GE 6G3706
I bought a GE T8 G8 432 ballast to replace three GE 6G3706 ballast. The old ballast required starters. The new ballast says I can use 3 or 4 tubes. I am using 3 36" 30 watt bulbs. The question is, I h… read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,821 satisfied customers
I am replacing a magnetic ballast (two tube T12) in a six foot
I am replacing a magnetic ballast (two tube T12) in a six foot fluorescent fixture with an electronic ballast. The wiring is different and I have three qualified opinions on how to connect the wires. … read more
Mike G.
Mike G.
Master Electrician
Vocational, Technical or Trade Scho
9,821 satisfied customers
my mother has one of old GE yellow counter tops with built
my mother has one of old GE yellow counter tops with built in sink, electric stove, panel with numerous outlets and fluorescent lights along the top.The GE 89G325 ballasts have died and I want to repl… read more
electrifier
electrifier
Master Electrician
Bachelor's Degree
1,458 satisfied customers
looking for a wiring diagram for a philips ballast #1cn2p32n
looking for a wiring diagram for a philips ballast #1cn2p32n . 5 wire black & white = line 2 blue and 1 red… read more
Jason
Jason
Service Technician
Associate Degree
4,922 satisfied customers
Disclaimer: Information in questions, answers, and other posts on this site ("Posts") comes from individual users, not JustAnswer; JustAnswer is not responsible for Posts. Posts are for general information, are not intended to substitute for informed professional advice (medical, legal, veterinary, financial, etc.), or to establish a professional-client relationship. The site and services are provided "as is" with no warranty or representations by JustAnswer regarding the qualifications of Experts. To see what credentials have been verified by a third-party service, please click on the "Verified" symbol in some Experts' profiles. JustAnswer is not intended or designed for EMERGENCY questions which should be directed immediately by telephone or in-person to qualified professionals.

JustAnswer in the News:

Ask-a-doc Web sites: If you've got a quick question, you can try to get an answer from sites that say they have various specialists on hand to give quick answers... Justanswer.com.
JustAnswer.com...has seen a spike since October in legal questions from readers about layoffs, unemployment and severance.
Web sites like justanswer.com/legal
...leave nothing to chance.
Traffic on JustAnswer rose 14 percent...and had nearly 400,000 page views in 30 days...inquiries related to stress, high blood pressure, drinking and heart pain jumped 33 percent.
Tory Johnson, GMA Workplace Contributor, discusses work-from-home jobs, such as JustAnswer in which verified Experts answer people’s questions.
I will tell you that...the things you have to go through to be an Expert are quite rigorous.

What Customers are Saying:

You did one super job of explaining to me everything there is to know about this fridge. I'm looking forward to asking you questions in the future.

JimmyBagley, IA

Wonderful service, prompt, efficient, and accurate. Couldn't have asked for more. I cannot thank you enough for your help.

Mary C.Freshfield, Liverpool, UK

This expert is wonderful. They truly know what they are talking about, and they actually care about you. They really helped put my nerves at ease. Thank you so much!!!!

AlexLos Angeles, CA

Thank you for all your help. It is nice to know that this service is here for people like myself, who need answers fast and are not sure who to consult.

GPHesperia, CA

I couldn't be more satisfied! This is the site I will always come to when I need a second opinion.

JustinKernersville, NC

Just let me say that this encounter has been entirely professional and most helpful. I liked that I could ask additional questions and get answered in a very short turn around.

EstherWoodstock, NY

Thank you so much for taking your time and knowledge to support my concerns. Not only did you answer my questions, you even took it a step further with replying with more pertinent information I needed to know.

RobinElkton, Maryland

< Previous | Next >

Meet the Experts:

Mike

Mike

Master Electrician

1,426 satisfied customers

Licensed Master Electrician - OnQ Certified Data Voice Audio Video Installer

Jason

Jason

Service Technician

4,922 satisfied customers

Over 20 years of experience in all types of installations, troubleshooting, and repairs.

Mike G.

Mike G.

Master Electrician

9,821 satisfied customers

Proven Professional 49 years Experience

Kevin

Kevin

Licensed Electrical Contractor

6,877 satisfied customers

34 years Licensed Electrical Contractor in Illinois, Adjunct College Electrical Instructor, Former Electrical Inspector, Diploma: Digital Electronics, FCC Amateur & Commercial Radio Licenses

electrifier

electrifier

Master Electrician

1,458 satisfied customers

Electrical contractor and electrical inspector for over 24 years with phone and networking expertise

Rich

Rich

Master Electrician

1,117 satisfied customers

Over 35 years residential, commercial, industrial wiring, install, troubleshoot, service, maintain

mrromex

mrromex

Electrical Technician

281 satisfied customers

over 40 years of all phases related to residential wiring and remodeling

< Previous | Next >

Disclaimer: Information in questions, answers, and other posts on this site ("Posts") comes from individual users, not JustAnswer; JustAnswer is not responsible for Posts. Posts are for general information, are not intended to substitute for informed professional advice (medical, legal, veterinary, financial, etc.), or to establish a professional-client relationship. The site and services are provided "as is" with no warranty or representations by JustAnswer regarding the qualifications of Experts. To see what credentials have been verified by a third-party service, please click on the "Verified" symbol in some Experts' profiles. JustAnswer is not intended or designed for EMERGENCY questions which should be directed immediately by telephone or in-person to qualified professionals.