The blower on my laars lx 250 will not start yet I get no error messages in the service panel. It worked yesterday.
Already Tried: I too cover off to see if there were any loose wires but everything looked connected.
Hi, I’m a moderator for this topic and I wonder whether you’re still waiting for an answer. If you are, please let me know and I will do my best to find a Professional to assist you right away. If not, feel free to let me know and I will cancel this question for you. Thank you!
I have not gotten an answer to my question.
Any chance of getting someone to answer this today
Sometimes, finding the right Professional can take a little longer than expected and we thank you greatly for your understanding. We’ll be in touch again shortly
chk to see if the fuse on the red wire is good.
I have checked the fuse and it was not blown, I checked to see that all the wires were not loose or broken and know the unit is getting power. Is it possible that ehhaust temp limit switch or the fuseable link is keeping the blower from operating? This unit fired up after the winter and one day heated the pool for a couple hours before failing to start the next day.
exhaust temp limit , fusible link or the water pressure switch will keep the heater from operating. i would start with the pressure switch.
Experience: CPO, Service & repairs over 16 years
Sorry but was away yesterday. one more question. I know the water pressure switch is operating and I changed both the exhaust temp limit switch and the fusible link. It started ran for about an hour and then shut down. Any thoughts would be appreciated.Tom